Description
Description
The C2W-BA Photoelectric Smoke Detector incorporates a state-of-the-art optical sensing chamber and an advanced microprocessor. The microprocessor allows the detector to automatically adjust its sensitivity back to the factory setting when it becomes more sensitive due to contaminants settling in its chamber. The C series Detectors contain a piezoelectric horn which generates a temporal pattern in an alarm condition. All C Series detectors on a zone will sound when the power supply to them is reversed. The C2W-BA also has two built-in LED status indicators, one red one green, to be used for testing and verification purposes.
Features
- Plug-in detector line, mounting base included
- Large wire entry port
- In-line terminals with SEMS screws
- Mounts to octagonal and single-gang backboxes, 4-square backboxes, or direct to ceiling
- Stop-Drop ’N Lock attachment to base
- Removable detector cover and chamber
- Built-in remote maintenance signaling
- Drift compensation and smoothing algorithms
- Simplified sensitivity measurement
- Wide angle, dual color LED indication
- Loop testing via EZ Walk feature
- Built-in test switch
Specifications
Sensitivity | 1.25 - 3.699 %/FT |
System Voltage | Nominal 12/24 VDC |
Min 8.5 VDC | |
Max 30 VDC | |
Max Ripple Voltage | 30 VDC |
Max Standby Current | 50 µA |
Peek Standby Current | 100 µA |
Max Start-up Capacitance | 0.1 µF |
Resources
System Sensor Website
Installation Guide
Datasheet