Description
Description
The Macurco GD-2A is a low voltage (12-24 VAC or VDC) electronic detector of combustible, heating type gases, that has been evaluated by ETL for methane (natural gas) and propane (LP) gas. The GD-2A is designed for connection to Fire Alarm / Burglary Control Panels. The GD-2A has a SPDT Alarm relay, for connection to control panels or other devices. The GD-2A does NOT detect carbon monoxide. The GD-2A does not have an internal audible sounder.
Features
- 12-24 VAC or VDC input
- Flush or surface mount enclosure
- N.O. or N.C. alarm relay
- N.C. trouble/supervisory relay
- Low maintenance 7-10 year solid-state sensor
- Coverage area: 900 sq. ft.
- Alarm setting 25% of LEL per UL 2075
- Detects heating gases: propane (LP) and natural gas (methane)
- Can be self-restoring or latching
- Electronic sensors: no maintenance or recalibration
- Temperature compensated
Specifications
Voltage | 12 to 24 VDC or VDC |
Current (non-alarm) | 45 mA @ 12 VDC, 22 mA @ 24 VDC, 65 mA @ 12 VAC, 45 mA @ 24 VAC |
Current (in alarm) | 70 mA @ 12 VDC, 35 mA @ 24 VDC, 100 mA @ 12 VAC, 65 mA @ 24 VAC |
Alarm relay rating | 0.125 AMPS, 40V, 3VA |
Trouble relay | 0.250 AMPS, 40V, 10VA |
Operating temperature range | 32° to 120° F |
Resources
Additional Information
Voltage: | 12 to 24 VAC |
Voltage: | 21 to 24 VDC |
Color: | White |