Fire-Lite I300A Addressable Monitor Module

CAD $62.43
Part Number:
I300A
UPC / EAN:
78386300587
Stock Number:
14253
Weight:
0.38 LBS
Shipping:
Calculated at Checkout

Description

Description

The Fire-Lite I300A is an addressable monitor module for Fire-Lite addressable fire alarm control panels. It is is a standard-sized module (typically mounts to a 4"  [10.16  cm]  square  box) that  supervises  either  a  Style  D (Class  A)  or  Style  B  (Class  B)  circuit  of  dry-contact  input devices, such as conventional heat detectors and pull stations.

The I300(A) Monitor Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC)  for normally-open-contact fire alarm and supervisory devices. The module has a panel-controlled LED indicator. The I300(A) can be used to replace M300(A)modules in existing systems.

Features

  • Built-in type identification automatically identifies this device as a monitor module to the control panel
  • Powered  directly  by  two-wire  SLC  loop.  No  additional power required
  • High noise (EMF/RFI) immunity
  • SEMS screws with clamping plates for ease of wiring
  • Direct-dial entry of  address: 01 – 159 on MS-9600 series panels, 01 – 99 on other compatible systems
  • LED flashes during normal operation and latches on steady to indicate alarm

Specifications

Normal operating voltage 15 to 32 VDC
Maximum current draw 5.0 mA (LED on)
Average operating current 375 μA (LED flashing), 1 communication every 5 seconds, 47k EOL
EOL resistance 47K ohms
Maximum IDC wiring resistance 1500 Ohms
Temperature range 32°F to 120°F (0°C to 49°C)
Humidity range 10% to 93% non-condensing
Dimensions 4.5" (11.43 cm) high x 4" (10.16 cm) wide x1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x2.125" (5.398 cm) deep box

Resources

Installation Instructions

Datasheet

Manufacturer's Website